Search:

Category

Control Cables

 View E-catalogue Here 

These cables are used for low volatge Electrical power station, indoor or Outdoor,all kinds of Industrial Applications.

Features

Standards as per IS – 1554 (Part-1)
Max. Conductor D.C. Resisitance at 200C conductor size 1.50 sq.mm – 12.1 W/km (Bare) and 12.2 W /km (Tinned copper) 2.50 sqmm – 7.41 W/km (Bare) and 7.56 W/km (Tinned Copper)

Control Cables

No.of Core & C.S.Area Thick of PVC Insul Thick of Inner Sheath Thick of Outer Sheath Approx. O.D. Approx. Net Wt of Cable
Current Rating
No. x “sq.mm” Nom.”mm” Min.”mm” “mm”(Nom) “mm” “kg/km” Direct in Ground “Amps” In Air/Duct “Amps”
2 x 1.50 0.80 0.30 1.80 11.8 185 23 20
3 x 1.50 0.80 0.30 1.80 12.3 190 21 17
4 x 1.50 0.80 0.30 1.80 13.2 225 21 17
5 x 1.50 0.80 0.30 1.80 14.1 260 16 14
6 x 1.50 0.80 0.30 1.80 15.1 295 15 13
7 x 1.50 0.80 0.30 1.80 15.1 315 14 13
10 x 1.50 0.80 0.30 1.80 18.4 425 13 11
12 x 1.50 0.80 0.30 1.80 18.9 480 12 10
14 x 1.50 0.80 0.30 1.80 19.8 535 11 10
16 x 1.50 0.80 0.30 1.80 20.7 595 11 9
19 x 1.50 0.80 0.30 2.00 22.5 720 10 9
24 x 1.50 0.80 0.30 2.00 25.8 880 9 8
27 x 1.50 0.80 0.30 2.00 26.3 960 9 8
30 x 1.50 0.80 0.30 2.00 27.2 1080 9 7
37 x 1.50 0.80 0.30 2.00 29.1 1230 8 7
2 x 2.50 0.90 0.30 1.80 13.0 230 32 27
3 x 2.50 0.90 0.30 1.80 13.6 240 27 24
4 x 2.50 0.90 0.30 1.80 14.6 290 27 24
5 x 2.50 0.90 0.30 1.80 15.7 335 23 19
6 x 2.50 0.90 0.30 1.80 16.9 385 21 18
7 x 2.50 0.90 0.30 1.80 16.9 420 20 17
10 x 2.50 0.90 0.30 1.80 20.8 570 18 15
12 x 2.50 0.90 0.30 2.00 22.2 690 17 14
14 x 2.50 0.90 0.30 2.00 23.2 775 16 13
16 x 2.50 0.90 0.30 2.00 24.3 860 15 13
19 x 2.50 0.90 0.30 2.00 25.5 985 14 12
24 x 2.50 0.90 0.30 2.00 29.4 1215 13 11
27 x 2.50 0.90 0.30 2.00 30.0 1330 12 10
30 x 2.50 0.90 0.30 2.00 31.0 1450 12 10
37 x 2.50 0.90 0.40 2.00 34.1 1790 11 9
No.x “sq.mm” Nom. “mm” Min. “mm” Strip Size Thick of PVC Outer Sheath “mm” min Approx. O.D. “mm” Approx. Net Wt of Cable “kg/km” Wire Dia “mm” Thick of PVC Outer Sheath “mm” min Approx. O.D. “mm” Approx. Net Wt of Cable “kg/km” Direct in Ground “Amps” In Air Dust “Amps”
2 x 1.50 0.80 0.30 1.40 1.24 13.6 415 23 20
3 x 1.50 0.80 0.30 1.40 1.24 14.1 430 21 17
4 x 1.50 0.80 0.30 1.40 1.24 15.0 490 21 17
5 x 1.50 0.80 0.30 1.40 1.24 15.9 545 16 14
6 x 1.50 0.80 0.30 1.40 1.24 16.9 605 15 13
7 x 1.50 0.80 0.30 1.40 1.24 16.9 630 14 13
10 x 1.50 0.80 0.30 1.40 1.40 20.6 835 13 11
12 x 1.50 0.80 0.30 4 x 0.80 1.24 19.5 760 1.60 1.40 21.5 950 12 10
14 x 1.50 0.80 0.30 4 x 0.80 1.40 20.8 830 1.60 1.40 22.4 1040 11 10
16 x 1.50 0.80 0.30 4 x 0.80 1.40 21.7 920 1.60 1.40 23.3 1130 11 9
19 x 1.50 0.80 0.30 4 x 0.80 1.40 23.1 1040 1.60 1.40 24.7 1265 10 9
24 x 1.50 0.80 0.30 4 x 0.80 1.40 26.4 1250 1.60 1.40 28.0 1510 9 8
27 x 1.50 0.80 0.30 4 x 0.80 1.40 26.9 1355 1.60 1.40 28.5 1610 9 8
30 x 1.50 0.80 0.30 4 x 0.80 1.40 27.8 1430 1.60 1.40 29.4 1700 9 7
37 x 1.50 0.80 0.30 4 x 0.80 1.40 29.7 1670 1.60 1.40 31.3 1960 8 7
2 x 2.50 0.90 0.30 1.40 1.24 14.8 500 32 27
3 x 2.50 0.90 0.30 1.40 1.24 15.4 520 27 24
4 x 2.50 0.90 0.30 1.40 1.24 16.4 590 27 24
5 x 2.50 0.90 0.30 1.40 1.24 17.5 660 23 19
6 x 2.50 0.90 0.30 1.40 1.24 18.7 745 21 18
7 x 2.50 0.90 0.30 1.40 1.24 18.7 780 20 17
10 x 2.50 0.90 0.30 4 x 0.80 1.40 21.8 900 1.60 1.40 23.4 1110 18 15
12 x 2.50 0.90 0.30 4 x 0.80 1.40 22.8 1020 1.60 1.40 24.4 1240 17 14
14 x 2.50 0.90 0.30 4 x 0.80 1.40 23.8 1130 1.60 1.40 26.5 1340 16 13
16 x 2.50 0.90 0.30 4 x 0.80 1.40 24.9 1210 1.60 1.40 26.5 1455 15 13
19 x 2.50 0.90 0.30 4 x 0.80 1.40 26.1 1355 1.60 1.40 27.7 1605 14 12
24 x 2.50 0.90 0.30 4 x 0.80 1.40 30.0 1655 1.60 1.56 32.0 1970 13 11
27 x 2.50 0.90 0.30 4 x 0.80 1.40 30.6 1770 1.60 1.56 32.6 2100 12 10
30 x 2.50 0.90 0.30 4 x 0.80 1.56 32.0 1940 1.60 1.56 33.6 2250 12 10
37 x 2.50 0.90 0.40 4 x 0.80 1.56 34.7 2300 2.00 1.56 37.1 2900 11 9

Download Our latest Brochure