Call Us Now : +022-25792011

Products

 
 
FRLS Cables Catalog

Size Dimension & Current Carrying Capacity
 

C.S.Area of Conduc- tor

Strands

Insulation Thickness (Nom.)

Overall Diameter (approx.)

Cond.Resistance Maxi. At 200C

Current rating

 

Casing/Caping

 

Concealed

 

mm˛

No. / mm

mm

mm

Ω/km

Amps

 

Amps

1.00

14/0.30*

0.70

3.00

18.10

12

 

11

1.50

22/0.30*

0.70

3.20

12.10

16

 

13

2.50

36/0.30*

0.80

3.80

7.41

22

 

18

4.00

56/0.30**

0.80

4.50

4.95

29

 

24

6.00

84/0.30**

0.80

5.50

3.30

37

 

31

 

 

 

 

 

 

 

 

*= Class-2 conductor, **= Class-5 conductor as per IS:8130


 
Colours

or customer specified

 

Flame Retardant Low Smoke cable - Properties

 

 

 

 

Sr.No.

Test Parameter

Reference Specification

Specification required

1

Critical Oxygen

ASTM-D 2863

29% minimum

 

Index

 

 

2

Temperature

ASTM-D 2863

2500C  minimum

 

Index

 

 

3

Smoke Density

ASTM-D 2843

40% maximum

 

Rating

 

 

4

Acid Gas

IEC 754

20% maximum

 

Generation (HCL)

 

 

 

 

 

 

   
 
 
 
 