Call Us Now : +022-25792011

Products

 
 
Miracle Green

Why Miracle Green?
As part of sustainable green building technology, to bringing down the use of hazardous PVC from your green building Miracle Green provide green cable solution. Normal PVC cables will be replaced with Green Cable.

Benefit to environment
PVC  is  not  only  hazardous  during  the  manufacturing  process but  also  potential  risk  in  case  of  fire. Green  Cable  is  superior  performance  cable  with  utmost  quality which is replacement for PVC cables.

Material of Construction
The cable construction with 99.97% pure best available copper of electrolytic grade, and EVA based insulation which gives the ultimate fire protection and minimal environmental hazards.

Human life invaluable

  • In a fire accident most people are killed due to smoke than the heat and fire.

  • Ordinary cable produce smoke & halogen acid

  • When people inhale smoke and halogen acid they lose ability to respond and escape

  • Fire spread faster in ordinary cable than Green Cable

Advantage

  • Excellent flame-retardancy
  • Halogen Free
  • Low smoke generation
  • Low toxic gas emission

Benefit

  • Better visibility help easy for people escape
  • Environment friendly
  • Fire retardancy Stop spreading of fire
  • Smoke free in case of fire accident

Application - Generally used where green environment and higher safety is expected for Human life and valuables

  • Airports

  • Centrally A. C. Buildings

  • Complexes

  • Educational Institutions

  • General House wiring

  • Green Buildings

  • High Raise Building

  • Hospitals

  • Hostels

  • Hotels

  • Public Places

  • Theaters

Size Dimension & Current Carrying Capacity
 

C.S.Area of

Strands

Insulation Thickness

Overall

Diameter

Cond.Resistance

Current rating

 

 

 

Conductor

 

 

(Nom.)

 

(approx.)

Maxi. At 20C

 

 

 

 

 

Casing/Caping

Concealed

 

 

 

 

 

 

 

 

 

mm

No. / mm

 

mm

 

 

mm

Ω/km

Amps

Amps

1.00

14/0.30*

0.70

3.00

18.10

12

11

1.50

22/0.30*

 

0.70

 

3.20

 

12.10

16

13

 

 

 

2.50

36/0.30*

 

0.80

 

3.80

 

7.41

22

18

4.00

56/0.30**

 

0.80

 

4.50

 

4.95

29

24

6.00

84/0.30**

 

0.80

 

5.50

 

3.30

37

31

 

*= Class-2 conductor, **= Class-5 conductor as per IS:8130

 

Zero Halogen Fire Retardant Compound Properties :-

 

Sr.No.

Test Parameter

Reference Specification

Specification required

1

Critical Oxygen Index

ASTM-D2863

29% minimum

2 Temperature Index

 ASTM-D2863

250C  minimum

3

Smoke Density Rating

ASTM-D2843

20% maximum

4

Acid Gas Generation (HCL)

IEC 754

Less than 0.50mg/gm

 
Colours

or customer specified

 

 
 
 
 